DO4P

I/O MODULE 2 analog inputs

61KZ010242 AI2CV

  • 2 analog inputs, software configurable
  •  12 bit resolutions
  • Stauts and diagnostic LEDs 

 Datasheet download  

 
 
 General data
Housing dimensions (width x height x depth)22.5 mm x 99.0 mm x 114.5 mm
Weight97 g (without connectors), 116 g (with  connectors)
Permissible operating temperature+5° to +55°C
Permissible storage and transport temperature-25° to +85°C
Permissible humidity10% to 95%, not condensing
Permissible air pressure (operation)80 to 106 kPa (up to  2000 m above sea level)
Permissible air pressure (storage and transport)70 to 106 kPa (up to  3000 m above sea level)
Degree of protectionIP20 according to IEC 60529
Connection method for connectorsSpring cage terminals
Conductor cross-section (power connector)0.2  to 2.5 mm2 (24 – 12 AWG)
Conductor cross-section (I/O connector)0.08 to1.0 mm2 (28 – 18 AWG)
Functional earth connectionTo the DIN rail with spring contact
Mode state visual indicatorsFault (FLT), status (STS) LED lamps

 

Power supply
Main power supply  VM124 V DC (-15% ÷ + 20% according to IEC 61131-2)
Maximum allowed ripple5% of supply voltage (according to  IEC 61131-2)
Current consumption from main supply1.5 A max (for external loads supply)
Supply overvoltage protectionBidirectional  Zener clamp (Vz > 30 V)
Supply reverse polarity protectionProtection diode, and safety fuse
Supply fuse2 A, not replaceable by the user
Local bus power supply5 V DC (fom local bus)
Local bus supply protectionsNone
Power presence visual indicatorsGreen LED lamp, lighted if main supply is present (PWR)
Max. current on VS pin1.5 A max.

 

Analog inputs
Number of inputs2, software configurable
Voltage inputs measuring range0-10 V
Voltage inputs typical impedance28.2 kΩ
Voltage inputs digital resolution12 bit
Voltage inputs measuring errort.b.d.
Voltage inputs temperature coefficient                                               t.b.d.
Current inputs measuring range0-20 mA
Current inputs digital resolution12 bit
Voltage inputs measuring errort.b.d.
Current inputs temperature coefficientt.b.d.
Inputs common potential isolation from GND500 VAC, funtional
Isolation between channelsNone
Input state visual indicatorsTwo orange LED lamps for every input, switched on if output 0-10 V (VPx) or output 4-20 mA (IPx) is active

 

Interface
Local busProprietary F3 IOs BUS
Moduli address settingWith rotary switch on front panel
Bus connectionsby TBUS connectors on  DIN rail
Interface circuitry protectionsESD protection
Level of ESD protection±8 kV (IEC 61000-4-2, contact discahrge)

 