AI4VP

I/O MODULE 2 analog outputs

61KZ010243  AO2CV

  •  2 analog outputs, 0-10 V  or 0-20 mA
  •  12 bit resolution
  •  Load range (voltage outputs): 1 kΩ to ¥
    Load range (current outputs): 0 Ω to 600 Ω
  • Status and diagnostic LEDs

 Download datasheet 

 

General data
Housing dimensions (width x height x depth)22.5 mm x 99.0 mm x 114.5 mm
Weight98 g (without  connectors), 117 g (with connectors))
Permissible operating temperature+5° to +55°C
Permissible storage and transport temperature-25° to +85°C
Permissible humidity10% to 95%, not condensing
Permissible air pressure (operation)80 to 106 kPa (up to  2000 m above sea level)
Permissible air pressure (storage and transport)70 to 106 kPa (up to 3000  m above sea level)
Degree of protectionIP20 according to IEC 60529
Connection method for connectorsSpring cage terminals
Conductor cross-section (power connector)0.2 to 2.5 mm2 (24 – 12 AWG)
Conductor cross-section (I/O connector)0.08 to 1.0 mm2 (28 – 18 AWG)
Functional earth connectionTo the DIN rail with spring contact
Mode state visual indicatorsFault (FLT), status (STS) LED lamps

 

Power supply
Main power supply  VM24 V DC (-15% ÷ + 20% according to IEC 61131-2)
Maximum allowed ripple5% of supply voltage (according to IEC 61131-2)
Current consumption from main supply1.5 A max. (for external loads supply)
Supply overvoltage protectionBidirectional Zener clamp (Vz > 30 V)
Supply reverse polarity protectionProtection diode, and safety fuse
Power Fuse2 A, not replaceable by the user
Local bus power supply5 V DC (from local bus)
Local bus supply protectionsNone
Power presence visual indicatorsGreen LED lamp, lighted if main supply is present (PWR)
Max. current on VS pin1.5 A max.

 

Analog outputs
Number of outputs2, 
Voltage output range0-10 V
Current  output range0-20 mA
Digital resolution12 bit
Voltage output permissible load1 kΩ to ¥
Current  output permissible load0 Ω to 600 Ω
Voltage output error0-20 mA
Current output errort.b.d.
Voltage output temperature coefficientt.b.d.
Current output temperature coefficientt.b.d.
Voltage output settling time for full-range change< 1 ms
 Current output settling time for full-range change < 1 ms
Outputs common potential isolation from GND                          500 VAC, Funcional
 Isolation between channelsNone 
Output state visual indicatorsTwo orange LED lamps for every input, switched on if output 0-10 V (VPx) or output 4-20 mA (IPx) is active

 

 

Interface
Local busProprietary F3 IOs BUS
Module address settingwith  rotary switch on front  panel
Bus connectionsby TBUS connectors on  DIN rail
Interface circuitry protections ESD protections
Level of ESD protection±8 kV (IEC 61000-4-2, contact discharge)

 

 